The table directly below indicates
the increase in heat transfer rate for a vertical heat
exchanger when the GeoClip is used.
|
Increase in heat transfer
rate of borehole using the GeoClip
|
|
¾
U-bend
|
1
U-bend
|
|
4.5 Bore
|
5 Bore
|
6 Bore
|
4.5 Bore
|
5 Bore
|
6 Bore
|
|
74.45%
|
78.65%
|
86.15%
|
65.82%
|
69.81%
|
76.94%
|
The table below shows the thermal
conductivity of bentonite grout and thermally enhanced
bentonite grouts which have silica sand added to them.
Under the GeoClip section an equivalent thermal
conductivity is given for each grout mixture, u-bend
pipe size and bore diameter using the GeoClip.
|
Grout material
|
Equivalent
borehole conductivity using the GeoClip
|
|
Bentonite
- lbs.
|
Silica
sand - lbs.
|
T.C. grout - Btu/hr.
ft °F
|
¾ U-bend |
1 U-bend |
|
4.5 Bore
Btu/hr. ft °F
|
5 Bore
Btu/hr ft °F |
6 Bore
Btu/hr ft °F
|
4.5 Bore Btu/hr ft °F
|
5 Bore
Btu/hr ft °F
|
6 Bore Btu/hr ft °F
|
|
50
|
0
|
0.45
|
0.79
|
0.80
|
0.84
|
0.75
|
0.76
|
0.80
|
|
50
|
50
|
0.57
|
0.99
|
1.02
|
1.06
|
0.95
|
0.97
|
1.01
|
|
50
|
100
|
0.69
|
1.20
|
1.23
|
1.28
|
1.14
|
1.17
|
1.22
|
|
50
|
150
|
0.80
|
1.40
|
1.43
|
1.49
|
1.33
|
1.36
|
1.42
|
|
50
|
200
|
0.91
|
1.59
|
1.63
|
1.69
|
1.51
|
1.55
|
1.61
|
|